Login
Trafo Engineering
⚡ Turnaround: 12–24 Hours 🛡️ 12 Months Warranty

Switchgear Repair

HT/LT Vacuum & Air Circuit Breaker Maintenance, Retrofitting & Busbar Servicing

Comprehensive maintenance, refurbishment, and retrofitting of 11kV/33kV Vacuum Circuit Breakers (VCB), Low-Voltage Air Circuit Breakers (ACB), Motor Control Centers (MCC), and copper busbar trunking systems.

Switchgear Repair
Trafo Heavy Engineering Workshop ISO 9001:2015 & IEC Certified Testing Facilities

Key Deliverables & Specifications

VCB Vacuum Bottle Dielectric Testing

28kV AC Hi-Pot test confirming vacuum integrity and arc quenching capability.

Micro-Ohm Contact Resistance Measurement

Precision 100A Ductor testing ensuring contact resistance remains < 40 micro-ohms.

Motorized Spring Mechanism Overhaul

Refurbishment of trip/close coils, charging motors, and mechanical anti-pumping relays.

Old Breaker Retrofitting Solutions

Custom retrofitting of obsolete oil/gas breakers with modern withdrawable VCBs.

Engineering Scope & Capabilities

HT & LT Switchgear Repair, Maintenance & Retrofitting

Switchgear panels protect your entire electrical distribution infrastructure. Trafo Engineering provides specialized maintenance, vacuum bottle replacement, contact timing diagnostics, and retrofitting for HT VCB panels (Schneider, ABB, Siemens, Trafo-Tech) and LT distribution boards.

Our Switchgear Engineering Scope

  • VCB Vacuum Bottle Integrity Testing: High-potential AC withstand testing (up to 28kV AC) to detect loss of vacuum before breaker failure.
  • Ductor Micro-Ohm Contact Resistance: Testing breaker primary jaw and tulip contacts to eliminate overheating contact resistance.
  • Mechanism Overhauling & Lubrication: Servicing spring-charge motors, trip coils, closing solenoids, and mechanical interlocks.
  • Busbar Retorquing & Insulation Shrouding: Retorquing high-tensile busbar bolts with calibrated torque wrenches and applying heat-shrink insulation boots.

Step-by-Step Engineering Methodology

1

Rack-Out Isolation & Visual Arc Chute Check

Racking breaker out to disconnected position, inspecting arc chutes and main contacts.

2

Contact Resistance & Timing Analysis

Measuring opening/closing speeds and pole simultaneity with digital breaker timer.

3

Mechanism Lubrication & Relay Tripping Test

Cleaning mechanism, applying synthetic grease, and validating secondary trip coil signals.

4

Primary Current Injection & Rack-In

Running primary current injection test to verify CT/relay loop before racking in.

Diagnostic & Calibration Instruments

Testing Instrument / Apparatus Capability & Standard Compliance
Circuit Breaker Timing Analyzer SCOT M3K Multi-Pole Breaker Analyzer
Contact Resistance Micro-Ohmmeter Megger MOM2 200A Micro-Ohmmeter
AC Hi-Pot Vacuum Tester Phenix 50kV AC Dielectric Test Set
Primary Current Injection Set 2,000A High-Current Injection System

Frequently Asked Technical Questions

Vacuum bottle degradation cannot be seen visually. We use high-voltage AC Hi-Pot test sets (applying 28kV AC across open contacts) to detect dielectric breakdown in failing bottles.
Yes, our retrofitting engineering team manufactures custom roll-in cassette adapters to fit modern Schneider or ABB VCBs into older panel enclosures.
⚡ Fast Response Guarantee

Book Switchgear Repair

Get an on-site engineer dispatched or receive a formal branded quotation.

Direct Engineer Line +880 1700-000000